© Böning Ship Automation. Image courtesy of Böning.

AHD-SAS 15 — Böning 15-Input Data Station

The Böning AHD-SAS 15 acquires binary and analogue sensor signals close to their source in distributed marine or industrial alarm and monitoring installations.

Original Product OEM Quality

Availability

TH 36 Marine StockAvailability on request
SKU: TH36-LP-001674
Category: ,
Brands:

Description

Overview

The Böning AHD-SAS 15 acquires binary and analogue sensor signals close to their source in distributed marine or industrial alarm and monitoring installations.

Operation and integration

Fifteen slots accept project-selected plug-in input modules for current, voltage, resistance, thermocouple and contact signals. Configurable characteristics accommodate nonlinear sensors and tank-volume curves. The acquired information is passed to the wider AMS/AMCS system for processing and visualisation; two CAN buses support redundant arrangements.

Key features

  • 15 configurable sensor channels
  • Optional autonomous monitoring, including exhaust-gas mean-value applications with special software
  • Serial expansion for up to 94 additional binary measuring points
  • Two serial outputs for equipment such as AHD-R101 or AHD 882
  • Two relay outputs for horn and collective alarm
  • Separate acknowledgement input

Technical specifications

  • Weight: Appr. 0.7 kg.
  • Operating temperature: -30°C … +70°C.
  • Storage temperature: -50°C … +85°C.
  • Degree of protection: IP 20.
  • Power supply: 24 V DC (+30% / -25%).

Additional information

Manufacturer product family

B⋮MACS – Data Stations

Dimension W x H x D

209 x 125 x 76 mm

Minimum installation height for CAN cable (M12)

116 mm

Weight

Appr. 0.7 kg

Operating temperature

-30°C … +70°C

Storage temperature

-50°C … +85°C

Degree of protection

IP 20

Required distance to compass

Standard magnetic compass: 0.40 m
Steering magnetic compass: 0.50 m

Power supply

24 V DC (+30% / -25%)

Current consumption

Max. 700 mA (24 V DC)

Interfaces

2 x CAN-Bus on terminal strip with DeviceNet connector (M12)
1 x RS232 (Sub-D9), internal use only

Inputs

15 x slot for binary and analog inputs, free and individually configurable with input modules according to project-specific configuration
2 x serial (opto-coupler) from binary data stations AHD-PS 15/30/47

Outputs

4 x potential-free relay contact, 30 V DC / 2 A max: (freely configurable)
2 x serial (opto-coupler) for relay station AHD-R101-2 or Spill Warning module AHD SW I/II

Module carrier housing

Installation directly on DIN rails TS 32 or TS 35

Approvals

DNV, CRS, LR, RS

Item Number

11663V02

Downloads